February 2005 Valves, Actuators & Pump Control

A feedback controller effectively calculates the amount of product that is required to be fed into the process. If, for example, the output (process demand - PD) of the controller is sitting at 50%, the controller is asking for a flow into the process of 50%. The process demand signal is fed to the control valve whose effective job is to `translate' this signal into a physical flow of the amount required. It stands to reason that the control can only be as good as the valve is capable of complying with the controller's demand signal.

As has been shown many times in this series of articles, the vast majority of problems encountered in feedback control loops are caused by valves. This article shows three interesting examples of severe control problems caused by valve problems. The examples are taken from work recently undertaken in a large metal refinery.

Figure 1 is an 'as found' closed loop test performed on an important flow loop. When the test was started it was seen that the flow was staying fairly constant, but with a small offset from setpoint. The output of the controller was hardly moving which would indicate the integral in the controller was far too slow.

Figure 1
Figure 1

A 10% setpoint change was then made and it can be seen how the flow overshot slightly and then stabilised below setpoint - again indicating poor tuning. However, about 20 seconds later, the flow suddenly and most unexpectedly shot up almost instantaneously by about 5%. (The controller then took quite a long time to get it back down to setpoint.) This jump was very strange as there was nothing in the process that could cause load changes of such a nature.

The open loop test which was then performed and which is shown in Figure 2 is absolutely amazing. As seen in the figure, the first two steps upwards are of different size, which could indicate non-linearity or possibly process saturation. The valve did not move on the first step in the reverse direction even though the PD moved by 10%. This would indicate hysteresis of at least 10%. On the next step the valve moved in a reasonable fashion. However, on the following step it gave a huge movement with some overshoot. The next step down took the PD to 40%. However, at this point the flow reached zero, which would indicate that the valve stroking was completely wrong.

Figure 2
Figure 2

The PD was then reversed again to open the valve. However, nothing occurred until the PD got up to 70%. This would now indicate a whopping valve hysteresis of 30! Two further steps on the PD were made on which the valve seemed to move reasonably. However, on the following step the valve suddenly went completely crazy, opening and shutting. The test was abandoned at this point.

It is impossible to control a process with such a valve. I always find things like this absolutely amazing. How could plant personnel not be aware that they have a problem valve like this? How did they manage to control this loop before, even in manual? I was told that it was an important loop.

The second example is also a flow loop where the control was supposed to be of critical importance.

Figure 3 shows the open loop test. It can be seen that on each reversal the PD had to be moved a great amount to try and get the valve to also reverse. Analysis of this uncovered a valve hysteresis of over 25%. (A general rule is that a maximum of 1% hysteresis is acceptable for valve with positioner). The test also revealed (from an examination of the relative step sizes of process variable and PD) that the valve was over twice oversized. (Control variance deteriorates directly proportionally to the amount a valve is oversized.)

Figure 3
Figure 3

The effect of hysteresis is that the PD has to move back right through the hysteresis band before the valve will start moving in the reverse direction. This results in the control being slowed right down and leads to increased control variance. With a 25% hysteresis and a valve that is over twice oversized, one would expect very poor control out of the loop, and this is exactly what was encountered in the final and very interesting closed loop test, part of which is illustrated in Figure 4. Small 5% setpoint changes were made first down and then up. It can be seen how the flow stayed constant with the valve 'stuck' until the PD has reversed through the 25%. It took 2 minutes, 15 seconds, to reverse the valve on each setpoint change!

Figure 4
Figure 4

The third example is of a flow loop that was unstable.

Figure 5 shows the closed loop 'as found' test. The flow looked fine at the start of the test. However, as soon as a setpoint change was made the loop went unstable. People often enquire as to why it was not unstable before the setpoint change was made. The normal reason for this is that operators in many plants very frequently, if not even normally, make changes in manual. They then place the controller in Auto after the change has been effected, and the process has settled out. The process is then likely to stay where it is, provided everything is steady, and the loop may not start cycling until a further setpoint or a load change occurs.

Figure 5
Figure 5

It is still again very worrying that nobody in the plant was aware that an important control loop like this was operating in this fashion - and quite likely to go unstable at any moment.

Figure 6 is the open loop test on this loop. It shows the very cyclic response of the valve on each step. Such a response is probably due to a positioner problem. Modern smart positioners very often contain their own internal P + D controllers which if not properly tuned can cause overshoots, or exhibit cycling that can often lead to unstable loop behaviour as seen here. Unfortunately time did not permit further investigations to be undertaken at the time these tests were performed.

Figure 6
Figure 6

I believe these examples once again illustrate how important it is that the valve does what the controller wants, if good control is to be achieved.

For more information contact Michael Brown, Michael Brown Control Engineering, 011 486 0567, [email protected], www.controlloop.co.za

Michael Brown is a specialist in control loop optimisation, with many years of experience in process control instrumentation. His main activities are consulting, and teaching practical control loop analysis and optimisation. He runs ESETA accredited training courses that can be held in clients' plants, where students can have the added benefit of practising on live loops. His work takes him to plants all over South Africa, and also to other countries.



Credit(s)



Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

Case History 198: Cascade control overcomes valve problems
Michael Brown Control Engineering Fieldbus & Industrial Networking
A large petrochemical refinery asked me to perform an audit on several critical base layer control loops. This article deals with a problem found on a valve controlling the flow of fuel to a heat exchanger.

Read more...
Ball valves and actuators optimise HVAC performance
Schneider Electric South Africa Valves, Actuators & Pump Control
Schneider Electric offers the full range of innovative SpaceLogic and EasyLogic ball valves and actuators. These cutting-edge products are designed to optimise HVAC system performance, ensuring comfort and energy efficiency in commercial and residential buildings.

Read more...
Alfa Laval expands hygienic valve portfolio
Valves, Actuators & Pump Control
Alfa Laval is expanding its hygienic valve portfolio by introducing the Unique SSV pressure relief valve and the Leakage Detection butterfly valve, alongside new smaller sizes of the Unique Mixproof CIP and Unique Mixproof process valves.

Read more...
Preparing pump systems for adverse weather conditions
Valves, Actuators & Pump Control
As the severity of storms in South Africa increases, so has the rush of sediment-laden water become a major issue and a significant challenge for irrigation. When sediment levels rise to just 10 grams per litre or more, the risk of pump wear and dam silting increases dramatically.

Read more...
Loop signature 28: Things to consider when tuning.
Michael Brown Control Engineering Editor's Choice Fieldbus & Industrial Networking
I was giving a course at a remote mine in the middle of the Namibian desert. We were discussing tuning responses, and as I always do on my courses, I mentioned that in my opinion ¼ amplitude damped tuning is not desirable, and is in fact not good.

Read more...
High-flow solenoid valve
Emerson Automation Solutions Valves, Actuators & Pump Control
Emerson has introduced the new ASCO Series 327C solenoid valve, which features a direct-acting, high-flow design that provides superior flow-to-power ratio. It permits high flows at minimum power levels, making it ideal for use in power plants, refineries, and chemical processing facilities.

Read more...
Case History 197: Bad reboiler temperature control.
Michael Brown Control Engineering Editor's Choice Flow Measurement & Control
It is very important that reboiler temperature controls operate well in petrochemical refineries, or the product quality can really suffer. I was asked to check such a control in a refinery where they were having problems with one of these controls.

Read more...
Proportional cartridge valve series is the fastest in its class
Valves, Actuators & Pump Control
Parker Hannifin is introducing the enhanced version of the proportional cartridge throttle valve series, TFP. The new pilot valve further reduces the step response times by up to 30%, making the TFP the fastest valve in its class.

Read more...
Proportional cartridge valve series is the fastest in its class
Valves, Actuators & Pump Control
Parker Hannifin is introducing the enhanced version of the proportional cartridge throttle valve series, TFP. The new pilot valve further reduces the step response times by up to 30%, making the TFP the fastest valve in its class.

Read more...
Inspection system for leak detection in valves in hazardous areas
Extech Safety Systems Valves, Actuators & Pump Control
Leaking valves in industrial plants not only lead to loss, safety risks and possible contamination and pollution, but also result in high economic costs. Therefore, valves in hazardous areas require regular proper inspection and preventive maintenance to ensure their functionality.

Read more...









While every effort has been made to ensure the accuracy of the information contained herein, the publisher and its agents cannot be held responsible for any errors contained, or any loss incurred as a result. Articles published do not necessarily reflect the views of the publishers. The editor reserves the right to alter or cut copy. Articles submitted are deemed to have been cleared for publication. Advertisements and company contact details are published as provided by the advertiser. Technews Publishing (Pty) Ltd cannot be held responsible for the accuracy or veracity of supplied material.




© Technews Publishing (Pty) Ltd | All Rights Reserved