Editor's Choice


Digital controllers: Part 9 - Integral or reset windup

June 2023 Editor's Choice

As mentioned in an earlier article in this Loop signature series, the integral or I term in the controller is a brilliant thing. It is an extremely elegant and simple solution for eliminating offset in control. However, like everything else in this world, virtually everything good has its bad side as well. In the case of the I term, its bad feature is that it never gives up trying to get rid of offset, even if it cannot be eliminated.

Many of our control problems stem from the integral continuously working to try and eliminate offset. Some examples of these are stick-slip cycling on self-regulating processes and continuous cycling on integrating processes with hysteresis on the valve, which have already been discussed in earlier articles. In addition, another problem can arise from the same cause, and this is known as integral or reset windup.

Integral windup occurs when a continuous error exists which cannot be eliminated. To take an example, imagine that an isolating valve in series with the control valve is closed, and the controller is left in automatic. At this point, let us imagine that the process variable (PV) goes to zero. The integrator in the controller will immediately start integrating to try and eliminate the error. This will result in the PD (controller’s output) increasing at the ramp rate of the integrator. As the error cannot be reduced, this will continue until eventually the PD reaches a maximum limit (normally set to 20 mA in most controllers).

However it must be remembered that in theory, the integrator’s output will continue to carry on ramping for as long as the error exists. In reality, in the old days of pneumatic and electronic analogue controllers, this could only continue until a physical limit such as air supply pressure, or a bus voltage, was reached. At this point it was said that the integrator was ‘saturated’ or fully ‘wound up’.

The situation is different in a digital computer. The integral is now not a voltage or pressure, but a number, and modern computers can deal with extraordinarily high numbers. Therefore, unless the controller manufacturer does something about it, the integrator could carry on virtually until the output reaches a value close to infinity. This is illustrated in Figure 1.

Eventually when the process is restarted, and the isolating valve reopened, fluid will flow through the fully open control valve. The PV will then start rising towards setpoint. However, due to the nature of an integrator, the PD cannot start reducing, and hence the control valve cannot start closing, before setpoint is reached. Figure 2 helps explain this. Essentially the integrator’s output cannot be reduced until the error signal on its input changes sign. This is because the integrator’s output will always rise as long as any positive error exists. If the error reduces to zero, the integrator’s output then remains constant. It can only start moving down after a negative error signal occurs. This means that the integrator can only start responding again once the PV has moved through the setpoint.

If the integrator has wound up, it means that it may take a long while for the integrator’s output to drop far enough to allow the PD to start moving down again, and at that point it would allow the control valve to also start closing. By this time an enormous process overshoot could have occurred.

To overcome this problem, most of the controller manufacturers incorporate a strategy, often referred to as ‘anti-reset windup’, to prevent the integral from winding up. The method used varies from manufacturer to manufacturer, but most of them ‘freeze’ the integral unit’s operation when the PD reaches low or high limits (generally at 4 and 20 mA.). At this point the output of the integrator remains constant at the last calculated value, and does not carry on winding up.

This method of anti-reset windup still does not prevent overshoots, as again the integrator cannot start decreasing until the error actually reverses at the point the PV reaches setpoint. However the overshoots will be much smaller than they would have been if no anti-reset windup had been employed.

Some of the manufacturers employ more sophisticated methods of anti-reset windup, which can limit the overshoot even more. Typically one of them works as follows (refer to Figure 3, for a graphical description).

When a controller winds up, it effectively forces the proportional band fully away from the setpoint, in fact all the way to the far side of the setpoint. The method used in this particular case is that when the controller detects windup, it artificially forces the proportional band to move back in the opposite direction to the windup, so that it’s other side is now forced down against the setpoint. In this manner the controller will start reacting as soon as the PV re-enters the proportional band after the control is coming back to normal. Effectively the method reduces the value of the integral to enable this procedure to take effect.

External anti-rest windup

There are certain other situations where it is also important to be able to freeze the integral from an external signal. This is sometimes known as ‘external anti-reset’ windup. Two cases in particular are where more than one controller is connected to the same valve.

The first of these is ‘over-ride’ or ‘selective’ control systems. This control strategy is frequently used for turbo-compressor anti-surge control. Various parameters like output pressure and flow can reach a value where a surge can occur through the compressor. At these limiting values, the output of the compressor needs venting. A controller is provided for each limiting parameter, the outputs of which generally pass to the vent valve via a high or low signal selector. Whichever controller’s output is the highest or lowest respectively takes over the control of the valve. The other controllers will then tend to wind up. It is therefore essential that their integrals be prevented from doing this by freezing them at their last values.

The second case is in cascade control systems, which were discussed in the previous Loop Signature article. Remember the master control loop is generally at least 10 times slower than the slave loop. If the slave controller’s output reaches a high limit, at which point its own anti-reset wind-up protection will come in to freeze its integral, then it is very important to also freeze the master controller’s integral to prevent it from integrating further. Huge overshoots can occur if this is not done.

It should be noted that most of the DCS systems do take this into account and provide such a feature. Unfortunately very few PLC manufacturers seem to be aware of this, and seldom make provision for external anti-reset windup.

About Michael Brown


Michael Brown.

Michael Brown is a specialist in control loop optimisation, with many years of experience in process control instrumentation. His main activities are consulting and teaching practical control loop analysis and optimisation. He now presents courses and performs optimisation over the internet.

His work has taken him to plants all over South Africa and also to other countries. He can be contacted at: Michael Brown Control Engineering CC, +27 82 440 7790


Credit(s)



Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

Connecting every transport node
RJ Connect Editor's Choice Data Acquisition & Telemetry
Stockholm's bus system strategically links urban mainline, suburban mainline, non-mainline routes, community service buses and night buses. To acquire and process data from multiple sources and analyse onboard information on their moving buses, Transdev sought a dependable and powerful onboard computer. It teamed up with CatAB, Moxa’s local representative, known for delivering top-notch industrial data communication boards and equipment since 1988.

Read more...
Local range of planetary units
SEW-EURODRIVE Editor's Choice Motion Control & Drives
As SEW-EURODRIVE South Africa actively extends its offerings to customers, the SEW PPK and SEW P2.e industrial gearbox ranges are good examples of solutions that are well suited to the local business environment.

Read more...
Case History 195: Unstable reboiler steam flow
Michael Brown Control Engineering Editor's Choice
A high-pressure steam flow control in a reboiler on a column in a petrochemical refinery continually cycled when placed in automatic. Several attempts had been made to tune the controller, but these had been unsuccessful.

Read more...
Open control system for retrofit of conveyor control system
Beckhoff Automation Editor's Choice
For every online retailer, warehouse logistics is part of the critical infrastructure. An Australian office equipment supplier has retrofitted the warehouse logistics installation of its central warehouse, and replaced the proprietary decentralised controllers of the conveyor lines with PC-based control from Beckhoff, based on powerful EtherCAT communication.

Read more...
Digital industrial platforms and why they are important
Editor's Choice
One of the most significant trends driving digital transformation is the emergence of digital industrial platforms. This article will briefly explore what digital industrial platforms are, why they are important, and how they might shape the future of industrial automation.

Read more...
Celebrating 65 years: rebuilding and redefining its legacy
Editor's Choice News
Founded in 1959 by Neill Simpson, Axiom Hydraulics has grown into one of South Africa’s elite hydraulic companies. Over the past six and a half decades they’ve weathered many challenges, but none as devastating as the fire of 2023.

Read more...
Young robotics team takes world title
igus Editor's Choice News
In an inspiring demonstration of innovation and teamwork, Texpand, a young South African robotics team, recently made history by winning the 2024 FIRST Tech Challenge World Championships.

Read more...
SAIMC: It’s not black and white
SAIMC Editor's Choice SAIMC
Grey imports are a problem worldwide, not least in the automation industry in South Africa. The Supplier Advisory Council (SAC) operates under the umbrella of SAIMC, and is tackling this problem head-on.

Read more...
Loop signature 25: Tuning part 3 - Results of tuning a particular simple self-regulating process by several different methods.
Michael Brown Control Engineering Editor's Choice
A couple of SWAG methods of tuning were given in the previous Loop Signature article. I have tuned a simple self-regulating process using those methods, and two other tuning methods, one of them being the sophisticated Protuner tuning package, which is the system I employ. The tests were performed on a very accurate and powerful simulation package, and the results are compared below.

Read more...
PC-based control for advanced hydrogen storage technology
Beckhoff Automation Editor's Choice PLCs, DCSs & Controllers
The proportion of renewable energies from solar, wind and water is rising continuously. However, sufficient storage options are of the essence to use these energies as efficiently as possible. GKN Hydrogen offers a particularly compact and safe option, low-pressure metal hydride hydrogen storage systems with PC-based control from Beckhoff.

Read more...