Editor's Choice


Loop Signatures 17 - How to make a bad valve into a good valve.

April 2023 Editor's Choice PLCs, DCSs & Controllers

People often have little realisation as to how badly a faulty valve can affect the performance of the control of the loop. Figure 1 shows the response of a slow temperature control loop to a setpoint change. In the test, taken over nearly two hours, the loop has still not stopped cycling. It looks like it has been terribly badly tuned. However, at the time of this test it was determined that the control valve suffered from a hysteresis of 6,8%, which is extremely bad (see earlier loop signature articles dealing with hysteresis).

Figure 2 shows the response of the same loop after the valve had been replaced with a good one. What may be hard to believe is that the tuning has not been changed at all since the previous test. On the setpoint change, the process reached the new setpoint and settled out quickly within a few minutes. All the cycling was caused by the integral term in the controller trying to get the valve to move to the correct place. This is an incredibly good example of why one cannot afford to use bad valves on slow processes.

Figure 3 shows a heat exchanger being controlled by a single temperature controller. The temperature of the process fluid is the input to the controller, and the controller’s output is fed directly to the steam valve. This method of control is not an ideal method of controlling any slow process, and in particular in the case of a heat exchanger it is particularly bad. There are two reasons for this. Firstly, any slow process like this exchanger can only be tuned very slowly, because when tuning self-regulating processes one generally sets the integral term in the controller close to the dominant time constant of the process. This often means integral times of many minutes per repeat.

With slow settings like this, the controller can only make slow corrections if any load disturbances arise. In the case of the heat exchanger under discussion, the steam is fed from a header that has other take-offs leading from it. This can result in fluctuations of pressure in the header. If, for example, the header steam pressure suddenly dropped by 3% as steam was drawn off to another process, the steam flow to the exchanger would be reduced. The controlled temperature would then slowly start to drop. The controller with its slow integral would take a long time to catch and correct this, and large control variance would result. Secondly, any valve problems like hysteresis cause havoc in slow control loops with long integral settings, as can be seen in Figure 1, and as discussed in previous articles.

Now, what one must realise is that the output of a controller sets the position of the valve stem. If the valve was perfect without hysteresis, had linear installed characteristics, and there were constant pressure conditions in its feed line, then this would result in achieving the correct amount of flow

through the valve to satisfy the dictates of the controller. In reality, valves are seldom perfect and there is no guarantee that the stem will move to the position as dictated by the controller (particularly with hysteresis in the valve). Secondly, it may not have completely linear installed characteristics, and thirdly, if pressure variations in the line can occur (as in this case), then the correct flow through the valve will definitely not be obtained.

If it were possible to ensure that the correct flow rate did follow the controller’s output, as would happen if we had a perfect valve, then the problems would be overcome. So how then can one make a real valve with its problems into a perfect valve?

The answer is very simple. One makes use of a technique called cascade control, whereby a second controller is used to control the flow of fluid through the valve. (This obviously also involves having to install a flowmeter in the steam line). This new configuration is shown in Figure 4.

Flow controllers are tuned with parameters that are lightning fast compared with those in the temperature controller. The time constant of a flow loop is in the order of one or two seconds, which is what the integral is set to in the flow controller. This means that the flow controller is capable of correcting for problems like line pressure variations, non-linearity and hysteresis in the valve relatively quickly, so the temperature process will not be affected. Even if the flow loop suffers from something like stick-slip cycling, and relatively bad hysteresis, the average flow through the valve will probably be more than good enough to keep the temperature on setpoint.

Terminology used can differ widely. As mentioned in previous articles there are no standards in control. The temperature loop can be called the primary, master or outer loop, and the flow loop the secondary, slave, or inner loop, respectively.

Cascade control can really work brilliantly, even as mentioned above, with relatively poor valves. As discussed, it effectively takes the valve problems out of the equation, including variations in pressure in the valve line, and in fact could be said to have made a bad valve into a good one.

In general, I believe that cascade control is almost mandatory for any critical slow control process in a plant. I have often persuaded plants to install cascade systems on important slow loops with absolutely excellent results, and resulting in vastly improved control performance and variance.

Cascade systems are typically found with the following combinations:

Sometimes people become very confused about the purpose of cascade control, and I have often heard process operators expressing the opinion that it is stupid having two controllers to control only one valve. Confusion also often reigns when it comes to level control with a cascaded flow control on the valve. Many plant personnel believe the level controller is there to keep the level constant, and the flow controller is there to keep the flow constant. Unfortunately, the second law of control states that you can only control as many variables as you have valves, so it doesn’t work that way. I often have quite a job explaining that the only reason for flow control is to ensure that the valve does its job correctly.

In passing, I would mention that this combination is particularly effective, as level is an integrating process, which is very likely to cycle continuously with any hysteresis in the valve. Control will also be adversely affected with any non-linearity in the valve. Adding the flow loop now takes the valve out of an integrating loop and puts it into a self-regulating loop, which is faster and subject to far fewer problems.

One very important point to remember is that cascade control can only work really well if the secondary process is ideally ten times faster than the primary process. Why? The reason is that cascade loops are interactive. If they both have similar response times they will tend to fight each other and could be very cyclic. A general rule of thumb is that if the secondary is less than about six times faster than the primary, then it may be better to dispense with the cascade entirely.

This article was written in the evenings during a course recently presented at a petrochemical plant in Saudi Arabia. A delegate asked me what I meant by the ‘speed’ of a process, and if this term also includes the controller tuning. The speed of a process is best judged by the ultimate frequency of that process. (Note: The ultimate frequency is the frequency at which the loop oscillates with sufficient gain inserted in a proportional-only controller). Another, and rougher, method of judging speed is by looking at the response time of the process to a step change on the input.

In conclusion, I would urge people to try using cascade control on slow and important loops where performance is not as good as desired. If it is set up properly the results will be very rewarding.


About Michael Brown


Michael Brown.

Michael Brown is a specialist in control loop optimisation, with many years of experience in process control instrumentation. His main activities are consulting and teaching practical control loop analysis and optimisation. He now presents courses and performs optimisation over the internet.

His work has taken him to plants all over South Africa and also to other countries. He can be contacted at: Michael Brown Control Engineering CC, +27 82 440 7790,


Credit(s)



Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

Loop signature: Tuning part 4 processes
Michael Brown Control Engineering Editor's Choice Fieldbus & Industrial Networking
The purpose of this particular article is to try and give those unfortunate enough to have to use SWAG (scientific wild ass guess) tuning a bit of an idea of how to go about it, and even more importantly some understanding of a couple of basic principles.

Read more...
EtherCAT and PC-based control elevate next-generation laser cutting machine
Beckhoff Automation Editor's Choice
Cincinnati Incorporated has been building sheet metal processing equipment for 125 years. Since the switch to PC-based control, the only limits to development have been physical.

Read more...
Ensure seamless integration and reliable performance with CANbus solutions
RJ Connect Editor's Choice Fieldbus & Industrial Networking
Modern industrial applications require robust and effective communication. The CANbus product range guarantees smooth integration and data transfers throughout systems.

Read more...
Connecting every transport node
RJ Connect Editor's Choice Data Acquisition & Telemetry
Stockholm's bus system strategically links urban mainline, suburban mainline, non-mainline routes, community service buses and night buses. To acquire and process data from multiple sources and analyse onboard information on their moving buses, Transdev sought a dependable and powerful onboard computer. It teamed up with CatAB, Moxa’s local representative, known for delivering top-notch industrial data communication boards and equipment since 1988.

Read more...
Local range of planetary units
SEW-EURODRIVE Editor's Choice Motion Control & Drives
As SEW-EURODRIVE South Africa actively extends its offerings to customers, the SEW PPK and SEW P2.e industrial gearbox ranges are good examples of solutions that are well suited to the local business environment.

Read more...
Digitalised recycling systems
ifm - South Africa Editor's Choice
The EREMA Group develops and produces plastics recycling systems. The approximately 7500 active plants worldwide have the capacity to produce more than 20 million tons of recycled granulate. With up to 80 vibration sensors per system, EREMA relies on sensor technology and IO-Link masters from ifm to control the manufacturing process.

Read more...
VEGA fights incorrect measurements
VEGA Controls SA Editor's Choice
VEGA’s 80  GHz radar sensors, with their 120 dB dynamic range, ensure full visibility in all process conditions, overcoming interference and obstacles that standard sensors find challenging.

Read more...
Helping mining customers achieve balance
Endress+Hauser South Africa Editor's Choice
The mining industry faces several ESG challenges, particularly in relation to water stewardship, water licensing, water quality monitoring, and emission monitoring. Fortunately, Endress+Hauser is well positioned to help mines achieve their commitments in these areas.

Read more...
Keep the ball rolling
Bearing Man Group t/a BMG Editor's Choice Motion Control & Drives
BMG’s Fluid Technology team has recently completed the design, supply and commissioning of an advanced lubrication system for a main bearing on a ball mill, which has been developed to optimise productivity and minimise maintenance requirements and downtime.

Read more...
Case History 195: Unstable reboiler steam flow
Michael Brown Control Engineering Editor's Choice
A high-pressure steam flow control in a reboiler on a column in a petrochemical refinery continually cycled when placed in automatic. Several attempts had been made to tune the controller, but these had been unsuccessful.

Read more...