Editor's Choice


Case History 184: Why couldn’t they tune the loops to get good control?

October 2022 Editor's Choice

I never get tired of showing people how important it is to troubleshoot a control loop before trying to tune it, as so many people think tuning will overcome all problems. This month’s article covers two examples where all the tuning in the world would not have achieved good control.

Example 1: The sticky valve

In the first example, the operators in a petrochemical refinery were having trouble trying to control the flow of a light end-product, and had resorted to trying to run the loop in manual. However, from time to time there were quite a few load disturbances which affected the flow badly, and they had to frequently revisit the loop to make adjustments.

Figure 1 is a closed-loop test ‘as found’ (ie, with the original tuning in it). At the start of the test, one can see that the process value (PV) is slowly drifting up to the setpoint (SP) and, after about 10 minutes, finally reaches it. The SP was then stepped up by a small 2% after which the PV moved up but then seemed to settle before reaching the SP.

The controller output (PD) had moved up by about 20%, and was still rising quite steeply when the SP was stepped down by 2% again. At this stage the PD came down very quickly, but it took the PV quite a while before it, too, started moving down. This is a sign of the valve not moving and indicates that there is hysteresis or stickiness in the valve. The PV finally got back down to the SP with the PD well below the value it had been at the start of the step-up in SP. This would confirm that there is probably bad hysteresis in the valve.

The open-loop test is shown in Figure 2, in which the following can be seen:

a) When the PD is below about 40%, the PV responds well to steps in the PD. When the PD is above that, the steps in PV are very much smaller, and became smaller the higher the PD was stepped. Although there is a chance that there is something strange with the installed characteristics of the valve, it is far more likely that the flow is reaching a point of saturation, probably due to insufficient pressure in the pipe.

b) The process gain of the loop is about 0,5 – based on the lowest step changes. This is usually a sign that the flow transmitter has too wide a span, but this might not be the case if the flow could have reacted better if there were more pressure in the pipe.

c) There is no real indication in this test of valve hysteresis or stickiness, but it must be taken into account that these things do not always show when a valve is reacting to step changes in PD.

A final closed-loop test was carried out with improved tuning, and this is shown in Figure 3. It can be seen that the valve was in fact extremely sticky, and taking a long time to react to many of the SP changes. Unfortunately, the plant needed to keep the SP at around 50%, where it was in the saturation region, and this is a case where the plant needed to try and increase the pressure to get the flow to react properly, and also the valve needed servicing. Only then would it be able to attain good control.

Example 2: Waste gas flow

The second example is even more dramatic. The loop’s purpose was to control the flow of waste gas to the flare in the same plant as above, which is quite an important control in such plants. The problem was that the flow followed the setpoint, but cycled quite wildly about it.

Figure 4 shows the closed-loop ‘as found’ test with changes in SP being made, and it can be seen how badly and frequently the rapid fluctuations occurred.

Many people in the C&I; department had tried tuning the controller to stop the fluctuations, but all to no avail.

Figure 5 is the open-loop test, which immediately showed what was happening. The valve was jumping around badly and, upon changes in the PD signal, produced huge over- or under-shoots. Sometimes it didn’t respond properly at all, sometimes it cycled, sometimes it moved the wrong way, sometimes it stuck, sometimes it moved too much – all making it very non-repeatable.

This is one of the most interesting and dramatic examples I have seen of a valve not following the PD signal properly. Luckily, the fluctuations were all in a relatively narrow band, so an average flow control was possible. Another interesting thing is that nobody in the C&I; department was aware of the problem, and all had tried tuning.

It was later found that the actual problems with the valve were that, first, there was some very bad play in loose linkages and that, second, the positioner had not been properly tuned.


About Michael Brown


Michael Brown.

Michael Brown is a specialist in control loop optimisation, with many years of experience in process control instrumentation. His main activities are consulting, and teaching practical control loop analysis and optimisation. He now presents courses and performs optimisation over the internet.

His work has taken him to plants all over South Africa and also to other countries. He can be contacted at: Michael Brown Control Engineering CC, +27 82 440 7790, [email protected], www.controlloop.co.za


Credit(s)



Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

The AI skills every engineer now needs
Editor's Choice
To use AI responsibly and effectively, you need at least a basic understanding of how they work and where they can fail. Generative AI then becomes a powerful assistant; without it, you are effectively ‘prompting and praying’, exposing yourself to errors and professional embarrassment.

Read more...
How to protect your industrial network
RJ Connect Editor's Choice Fieldbus & Industrial Networking
Network security is no longer a matter of preventing hacking or data breaches. Traditional defence mechanisms for perimeter protection may not fully address internal threats or device-level vulnerabilities alone.

Read more...
Elevating analogue signal processing
Endress+Hauser South Africa Editor's Choice
The RN Series from Endress+Hauser is a powerful and relevant solution for analogue signal processing and conditioning.

Read more...
Lifting the lid on bulk packaging
VEGA Controls SA Editor's Choice
Authorities impose strict requirements on pharmaceutical and cosmetic packaging. Choosing the right instrumentation, such as VEGA’s VEGAFLEX 83 for level measurement, helps manufacturers navigate the challenges with accuracy, reliability and compliance.

Read more...
The next generation of inductive scanning encoder solutions
ATI Systems Editor's Choice Sensors & Transducers
With the launch of the ECI 1122 and EQI 1134 rotary encoders, positioning specialist, HEIDENHAIN has introduced a new benchmark in inductive scanning technology that raises the bar for motion control and precision automation.

Read more...
Loop Signature Part 2-1: Loop signatures and process transfer functions
Michael Brown Control Engineering Fieldbus & Industrial Networking
The previous series of loop signature articles dealt with the basics of control loop optimisation, and concentrated on troubleshooting and ‘SWAG’ tuning of simple processes. In this new series, consideration will be given to dealing practically with more difficult issues like interactive processes, and with processes with much more complex dynamics.

Read more...
Machine health monitoring with ifm
ifm - South Africa Editor's Choice IT in Manufacturing
With ifm’s machine health monitoring, early signs of wear can be detected and unexpected failures prevented. Combined with equipment preventive maintenance software, interventions can be scheduled proactively to avoid costly downtime.

Read more...
Powering Africa’s sustainable mining
VEGA Controls SA Editor's Choice Level Measurement & Control
At the 2026 Mining Indaba in Cape Town, one theme rises above all others, progress through precision. For VEGA, a global leader in process instrumentation, this mission aligns perfectly with its core purpose, which is turning measurement into meaningful progress.

Read more...
PCS Global delivers turnkey MCC installation in Botswana
PCS Global Editor's Choice PLCs, DCSs & Controllers
PCS Global is delivering a turnkey containerised MCC installation for a major copper mining operation in Northwest Botswana.

Read more...
SEW-EURODRIVE transforms drivetrain uptime
SEW-EURODRIVE Editor's Choice Motion Control & Drives
The DriveRadar IoT Suite from SEW-Eurodrive is an ideal solution for industrial condition monitoring. This powerful ecosystem of intelligent sensors, edge devices and cloud-based analytics ensures that customers have full visibility and control of their operations.

Read more...









While every effort has been made to ensure the accuracy of the information contained herein, the publisher and its agents cannot be held responsible for any errors contained, or any loss incurred as a result. Articles published do not necessarily reflect the views of the publishers. The editor reserves the right to alter or cut copy. Articles submitted are deemed to have been cleared for publication. Advertisements and company contact details are published as provided by the advertiser. Technews Publishing (Pty) Ltd cannot be held responsible for the accuracy or veracity of supplied material.




© Technews Publishing (Pty) Ltd | All Rights Reserved