Editor's Choice


Control loop: Case History 170

January 2020 Editor's Choice

Michael Brown is a specialist in control loop optimisation with many years of experience in process control instrumentation. His main activities are consulting, and teaching practical control loop analysis and optimisation. He gives training courses which can be held in clients’ plants, where students can have the added benefit of practising on live loops. His work takes him to plants all over South Africa and also to other countries. He can be contacted at Michael Brown Control Engineering cc, +27 82 440 7790,

[email protected], www.controlloop.co.za

As mentioned in earlier articles, the integral (or I term) in the controller is a brilliant thing. It is an extremely elegant and simple solution for eliminating offset in control. However, like everything else in this world, it has its bad side as well. In the case of the I term, its bad feature is that it never gives up trying to get rid of offset, even when it cannot be eliminated.

Integral windup

Many control problems can stem from the integral, continuously working to try and eliminate offset. Some examples of these are stick-slip cycling on self-regulating processes, and continuous cycling on integrating processes with hysteresis on the valve, all of which have been discussed in earlier articles. In addition, another problem can arise from the same cause, known as integral or reset windup.

Integral windup occurs when a continuous error exists that cannot be eliminated. For example, imagine that an isolating valve in series with the control valve is closed, and the controller is left in automatic. At this point let us imagine that the PV (process variable) goes to zero. The integrator in the controller will immediately start integrating to try and eliminate the error. This will result in the PD (controller’s output) increasing at the ramp rate of the integrator. As the error cannot be reduced, this will continue until eventually the PD reaches a maximum limit (20 mA in most controllers).


Figure 1.

However, it must be remembered that in theory, the integrator’s output will continue to carry on ramping for as long as the error exists. In reality, in the old days of analog controllers, this could only continue until a physical limit was reached. At this point it was said that the integrator was ‘saturated’ or fully ‘wound up’.

The situation is different in a digital computer. The integral is now not a voltage or pressure, but a number, and modern computers can deal with extraordinarily high numbers. Therefore, unless the controller manufacturer does something about it, the integrator could carry on until the output reaches a value close to infinity. This is illustrated in Figure 1.

Eventually, when the isolating valve is reopened, the fluid will flow through the fully open control valve, and the PV will then start rising towards set point. However, due to the nature of an integrator, the PD cannot start reducing, and hence the control valve cannot start closing before the set point is reached. Essentially, the integrator’s output cannot be reduced until the error signal on its input changes sign. This is because the integrator’s output will always rise as long as any positive error exists. If the error reduces to zero, the integrator’s output then remains constant. It can only start moving down after a negative error signal occurs. This means that the integrator can only start responding again once the PV has moved through the set point. Figure 2 helps explain this.

Some practical examples

If the integrator has wound up, it means that it may take a long time for the its output to drop far enough to allow the PD to start moving down again, and at that point, it would allow the control valve to start closing. By then, an enormous process overshoot could have occurred, with long delays before the controller can start actually controlling again.

To cite an extreme example, a senior instrument technician on a gold mine gave me an example of one of their control loops that wound up after a plant trip occurred, and on restarting the plant, the output of the controller remained at full output for nine hours before it started moving down.


Figure 2.

A second interesting example I encountered recently was in a refinery. The problem was in a demineralisation plant with a water pressure controller. It occurred periodically when clean water was introduced to perform a rinse. The incoming water was at a much higher pressure, which backed off the controlled pressure and limited it to a value well below set point. This resulted in the integral action ramping up the PD to 100% (wind up). When the unit went back to normal operation, the pressure jumped above set point, and it then took many, many minutes for the output to get back down to the normal area where control could resume.

The result is that when the cleaning water is shut-off, the controlled pressure immediately jumped some 15% over set point. Although the proportional action does immediately drop the PD a bit, it took the integral a further 7.5 minutes to get the control back down to set point! The closed loop test annotated in Figure 3 shows it very well.

The problem can be eliminated by freezing the integral when the rinse begins, or else putting the controller into manual for the rinse period.


Figure 3.

During the course of my career, I have encountered quite a few problems caused by integral windup, and since in my experience very few people understand the workings of their controllers, the problem is not identified properly. In one particular case at a plant that made explosives, a cheap PLC controller that did not have any built in reset windup protection almost caused a serious explosion, as under certain conditions, the controller integral wound up resulting in potentially serious temperature overshoots. Luckily the high temperature trip system worked whenever this happened.

Two important points to remember to avoid reset windup:

1.As a general rule, integral action should always freeze when further movement of the controller’s output can have no further effect on the control.

2.In particular, in every case of an oversized valve, the integral should be frozen and a limit placed on the controller’s output where further movement of the valve can have no further effect on the PV. This will help prevent both reset windup, and valve windup. This is an important point as many plants have cases of (sometimes) hugely oversized valves or pumps.




Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

Loop signature: Tuning part 4 processes
Michael Brown Control Engineering Editor's Choice Fieldbus & Industrial Networking
The purpose of this particular article is to try and give those unfortunate enough to have to use SWAG (scientific wild ass guess) tuning a bit of an idea of how to go about it, and even more importantly some understanding of a couple of basic principles.

Read more...
EtherCAT and PC-based control elevate next-generation laser cutting machine
Beckhoff Automation Editor's Choice
Cincinnati Incorporated has been building sheet metal processing equipment for 125 years. Since the switch to PC-based control, the only limits to development have been physical.

Read more...
Ensure seamless integration and reliable performance with CANbus solutions
RJ Connect Editor's Choice Fieldbus & Industrial Networking
Modern industrial applications require robust and effective communication. The CANbus product range guarantees smooth integration and data transfers throughout systems.

Read more...
Connecting every transport node
RJ Connect Editor's Choice Data Acquisition & Telemetry
Stockholm's bus system strategically links urban mainline, suburban mainline, non-mainline routes, community service buses and night buses. To acquire and process data from multiple sources and analyse onboard information on their moving buses, Transdev sought a dependable and powerful onboard computer. It teamed up with CatAB, Moxa’s local representative, known for delivering top-notch industrial data communication boards and equipment since 1988.

Read more...
Local range of planetary units
SEW-EURODRIVE Editor's Choice Motion Control & Drives
As SEW-EURODRIVE South Africa actively extends its offerings to customers, the SEW PPK and SEW P2.e industrial gearbox ranges are good examples of solutions that are well suited to the local business environment.

Read more...
Digitalised recycling systems
ifm - South Africa Editor's Choice
The EREMA Group develops and produces plastics recycling systems. The approximately 7500 active plants worldwide have the capacity to produce more than 20 million tons of recycled granulate. With up to 80 vibration sensors per system, EREMA relies on sensor technology and IO-Link masters from ifm to control the manufacturing process.

Read more...
VEGA fights incorrect measurements
VEGA Controls SA Editor's Choice
VEGA’s 80  GHz radar sensors, with their 120 dB dynamic range, ensure full visibility in all process conditions, overcoming interference and obstacles that standard sensors find challenging.

Read more...
Helping mining customers achieve balance
Endress+Hauser South Africa Editor's Choice
The mining industry faces several ESG challenges, particularly in relation to water stewardship, water licensing, water quality monitoring, and emission monitoring. Fortunately, Endress+Hauser is well positioned to help mines achieve their commitments in these areas.

Read more...
Keep the ball rolling
Bearing Man Group t/a BMG Editor's Choice Motion Control & Drives
BMG’s Fluid Technology team has recently completed the design, supply and commissioning of an advanced lubrication system for a main bearing on a ball mill, which has been developed to optimise productivity and minimise maintenance requirements and downtime.

Read more...
Case History 195: Unstable reboiler steam flow
Michael Brown Control Engineering Editor's Choice
A high-pressure steam flow control in a reboiler on a column in a petrochemical refinery continually cycled when placed in automatic. Several attempts had been made to tune the controller, but these had been unsuccessful.

Read more...