Temperature Measurement


Common causes of thermocouple temperature measurement errors

April 2018 Temperature Measurement

Thermocouples are among the most popular temperature measurement instruments in industrial applications because of their versatility and ease of use. However, measurement errors can occur. They are robust temperature measurement devices that are accurate enough for many industrial and scientific applications. Relatively inexpensive compared to other temperature measurement technologies, thermocouples are valued for their ability to measure a wide temperature range from -200 to 1250°C.

Thermocouples measure temperature differentials, not absolute temperatures. Two wires, each made from a different metal, are joined at the tip. This is the measuring junction. At the other end, the wires are connected to a body of a known temperature, called the reference junction. A thermocouple works by taking the difference in voltage between the two junctions, explained by the Seebeck effect. The measured voltage is converted into a temperature unit, with the temperature reading displayed on a device or transmitted to a remote location.

Although thermocouples are reliable, temperature measurement errors can occur for various reasons. The following are the six most common causes of thermocouple measuring errors:

1. Selecting the wrong type of thermocouple on the transmitter

Problems can occur if the wrong type of thermocouple is chosen when inputting the settings into the transmitter during installation. This is a common error as there are numerous types of thermocouples – types K, J, N, E, T, R, S, and B – each with a different range, accuracy and electrical output.

Solution: Almost all thermocouples are colour coded by type, so all that is needed is to confirm the colour of the thermocouple jacket and match the settings on the transmitter.

2. Problems related to the thermocouple extension wire

If the polarity of the thermocouple lead wires is accidentally reversed, the measured temperature will be incorrect by the difference in temperature of the two ends of the leads. The problem is understandable because red is the usual colour for positive charges, whereas the red wire in thermocouple cables typically contains the negative signal. This colouration is ANSI standard for thermocouples, but it is not what most people expect.

Solution: Doublecheck the connection and, if necessary, swap the thermocouple lead wires.

3. Inherent variations in alloys

No two batches of wires are exactly alike. As the alloy percentages vary a tiny bit during each manufacturing process, some error in thermocouple accuracy is unavoidable. Standard thermocouples get within approximately 1% of the actual temperature at the measuring junction, which is accurate enough for most applications.

Solution: Order thermocouples with special-limit wires, which can improve accuracy twofold. These wires are manufactured at the highest tolerances to ensure the fewest possible impurities and the greatest consistency in alloy ratio.

4. Temperature variations around the reference junction connection

Because a thermocouple measures temperature differentials, any temperature fluctuations around the reference junction (cold junction), which has the known temperature, result in an erroneous temperature reading.

Solution: Make sure no fans or other sources of cooling or heating are located near the reference junction. Simple insulation can also protect the junctions from extreme temperatures.

5. Thermocouple grounded at more than one location

A thermocouple should be grounded at only one location. If it is grounded at more than one location, a ‘ground loop’ can be created with current flowing through the thermocouple from one ground to the other. This is likely to generate electromagnetic fields, which can lead to radio frequency interference related problems that can impact measurement accuracy.

Solution: Ground either the transmitter (connection head) or the controller/recorder, but not both. Selecting transmitters that have internal isolation between the input, output and ground usually provides enough isolation to eliminate a ground loop. Loop isolators are also available and can be put in the loop wiring circuit to prevent this from happening.

6. Thermocouple age

While thermocouples are reliable temperature measurement devices, they do drift with time. Maximum exposure temperature, cyclic measurements, and frequency of the cycles affect the metallurgy with a resultant drift, usually downward. Unfortunately, this drift cannot be predicted, but 5 to 10°C errors are common.

Solution: The only solution is to replace the thermocouple periodically based on the user’s experience.



Credit(s)



Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

Is the HVAC market in SA missing the big picture?
Iritron Temperature Measurement
The South African HVAC market is currently grappling with a pervasive mindset that prioritises lowest cost over value for money and technical excellence. However, this approach overlooks the significant benefits that come with investing in high-quality HVAC solutions.

Read more...
Temperature monitoring in dairies
ifm - South Africa Temperature Measurement
Milk is a natural product whose processing requires precise temperature settings. The Berchtesgadener Land dairy uses innovative temperature sensors from ifm in key process areas.

Read more...
Measuring temperature, relative humidity and dew point temperature
Senseca Temperature Measurement
Senseca’s range of passive or active transmitters measures temperature, relative humidity, and dew point temperature.

Read more...
High definition thermal imagers on steam crackers
Temperature Measurement
AMETEK Land’s high-definition thermal imaging system, the NIR-B-2K, has been selected by one the world’s largest ethylene producers for installation on multiple liquid-feed cracker furnaces.

Read more...
Magnetic field/temperature sensor with IO-Link
Turck Banner Southern Africa Temperature Measurement
Turck Banner’s CMMT condition monitoring sensor detects magnetic field changes on three axes, and thus opens up new application fields.

Read more...
Three ways to conduct thermal inspections
Comtest Temperature Measurement
There’s no universal solution for all infrared inspections with a Fluke thermal camera, also known as a thermal imager. You need to match your method to the type of equipment you’re inspecting and the level of detail you require.

Read more...
New temperature relative humidity and barometric pressure transmitter
Senseca Temperature Measurement
ENVIROsense, a new environmental temperature, relative humidity, relative humidity and, optionally, barometric pressure transmitter has been launched by Senseca, a leader in the design and manufacture of monitoring and measurement instrumentation.

Read more...
The role of alarm annunciators in temperature monitoring
Omniflex Remote Monitoring Specialists Temperature Measurement
Director at alarm annunciator specialist, Omniflex explores the importance of alarm annunciators in temperature monitoring applications, drawing on examples from different industrial settings.

Read more...
Increased safety and control in steel plants
Temperature Measurement
AMETEK Land has helped a major metals industry plant designer to enhance safety, control, and efficiency in steel plants.

Read more...
Industrial water heating solutions
Temperature Measurement
Electrolux (Kwikot) Industrial’s massive water heating tanks are making a name for themselves beyond local borders.

Read more...