Electrical Power & Protection


Signal isolators and loop interface 101 - Part 1

November 2006 Electrical Power & Protection

The ubiquitous problem with every plant is the interface of plant measurement signals to the monitoring and control systems. Unfortunately for many plants this is the single biggest area of weakness and with the success of the organisation depending on these measurements, more attention should be afforded to the integrity of signal conditioning systems.

The problems faced by these systems are numerous:

* Aged cabling.

* Long cable runs.

* Earth loops.

* Interference from other plant devices.

* Floating earth potentials.

* Isolation of signals from PLC, SCADA and DCS.

* Legacy instrumentation.

* Isolate grounded equipment.

* Adding instruments to existing loops.

* Poor design.

* Converting current loops into accurate 1-5 V.

* Protecting against open circuit loops.

* Load dependency calibration.

A compendium of common problems is addressed using loop powered isolators (LPIs) in this two-part article.

In Part 1 four applications will be looked at and in Part 2 in next month's issue, a further six applications will be dealt with.

Application 1: Using the LPI to isolate a powered 4-20 mA transmitter output from a resistive load

This is the basic circuit for inserting a loop powered isolator into a current loop. The LPI can simply be 'cut' into any existing current loop to isolate the current transmitter from the load.

Application 1
Application 1

Note: The 'IN' side of the LPI is always connected to the side of the loop supplying the loop power.

The LPI will consume less than 3 V of the available loop voltage. This is equivalent to inserting less 150 Ω of additional resistance into the current loop.

To determine the maximum loop resistance that you can tolerate in your cabling, apply the following formula:

RMAX = RT - RL - 150

where:

RMAX is the maximum resistance in the loop without causing measurement error (in Ω).

RT is the maximum load resistance that the current transmitter can drive (in Ω).

RL is the total resistance of all loads in the loop (excluding the LPI) (in Ω).

For reliable operation over the long term, you should design for less initial cable resistance than this maximum value. This provides a safety factor to account for increase in resistance of terminations and wiring with age or weathering.

A sensible value to use for this safety factor would be 100 Ω (equal to 2 V at 20 mA).

Application 2: Using the LPI to isolate a field-mounted 4-20 mA two-wire transmitter from a PLC, RTU or DCS

This is the basic circuit for isolating a field-mounted two-wire transmitter from the control circuitry using an LPI. The LPI can simply be 'cut' into any existing two-wire current loop to isolate the transmitter from the panel power supply.

Application 2
Application 2

NOTE: The 'IN' side of the LPI is always connected to the side of the loop supplying the loop power, so in this application the two-wire transmitter is connected to the OUT terminals of the LPI.

Because of the 2 mm² wire size capability of the LPI terminals, the LPI can also act as the field interface terminals, saving you the extra termination and wiring cost. For multiple loops where space is a concern, use the LPD dual module. (See Applications 7, 8 and 9 in Part 2 of this article).

The LPI will consume less than 3 V of the available loop voltage. This is equivalent to inserting less 150 Ω of additional resistance into the current loop.

To determine the maximum loop resistance that you can tolerate in your cabling, apply the following formula:

where:

RMAX is the maximum resistance in the loop without causing measurement error (in Ω).

VSmin is the minimum voltage of the power supply used to drive the loop (in V).

VTmin is the minimum voltage required by the two-wire transmitter for operation (in V).

RL is the total resistance of all loads in the loop (excluding the LPI) (in Ω).

For reliable operation over the long term, you should design for less initial cable resistance than this maximum value. This provides a safety factor to account for increase in resistance of terminations and wiring with age or weathering.

A sensible value to use for this safety factor would be 100 Ω (equal to 2 V at 20 mA).

Application 3: Using the LPI's internal resistor with a two-wire transmitter to provide 1-5 V to your PLC/RTU/DCS

There are many cases when using 4-20 mA inputs to your PLC or RTU or DCS is inconvenient. For example:

1. Your analog input does not support 4-20 mA, and mounting an external resistor is inconvenient.

2. Your analog input has plug in terminals, and you do not want to lose power to your field transmitter or disrupt the loop if the terminal block is unplugged.

Application 3
Application 3

In these cases you can use the internal resistor on the IN side of the LPI to conveniently convert your 4-20 mA signal into a 1-5 V signal. For the most accurate result, ensure that the 0 V reference of the LPI (terminal 8), and the 0 V reference of your analog input are referenced to the same point. Note: The 'IN' side of the LPI is always connected to the side of the loop supplying the loop power, so in this application the two-wire transmitter is connected to the OUT terminals of the LPI.Because of the 2 mm² wire size capability of the LPI terminals, the LPI can also act as the field interface terminals, saving you the extra termination and wiring cost.

The LPI will consume less than 3 V of the available loop voltage. This is equivalent to inserting less 150 Ω of additional resistance into the current loop.

To determine the maximum loop resistance that you can tolerate in your cabling in this application, apply the following formula:

where:

RMAX is the maximum resistance in the loop without causing measurement error (in Ω).

VSmin is the minimum voltage of the power supply used to drive the loop (in V).

VTmin is the minimum voltage required by the two-wire transmitter for operation (in V).

For reliable operation over the long term, you should design for less initial cable resistance than this maximum value. This provides a safety factor to account for increase in resistance of terminations and wiring with age or weathering.

A sensible value to use for this safety factor would be 100 Ω (equal to 2 V at 20 mA).

Application 4: Using the LPI's internal resistor with a four-wire transmitter to provide 1-5 V to your PLC/RTU/DCS

There are many cases when using 4-20 mA inputs to your PLC or RTU or DCS is inconvenient. For example:

1. Your analog input does not support 4-20 mA, and mounting an external resistor to convert the signal to 1-5 V is inconvenient.

2. Your analog input has plug in terminals, and you do not want to lose power to your field transmitter or disrupt the loop if the terminals are unplugged.

Application 4
Application 4

In these cases you can use the internal resistor on the OUT side of the LPI to conveniently convert your 4-20 mA signal into a 1-5 V signal.

For the most accurate result, ensure that the 0V reference to the LPI (terminal 5), and the 0V reference of your analog input are referenced to the same point.

Note: The 'IN' side of the LPI is always connected to the side of the loop supplying the loop power, so in this application the four-wire transmitter is connected to the IN terminals of the LPI.

Because of the 2 mm² wire size capability of the LPI terminals, the LPI can also act as the field interface terminals, saving you the extra termination and wiring cost.

The LPI will consume less than 8 V of the available loop voltage. This is equivalent to inserting less than 400 Ω of resistance into the current loop.

To determine the maximum loop resistance that you can tolerate in your cabling in this application, apply the following formula:

RMAX = RT - 400

where:

RMAX is the maximum resistance in the loop without causing measurement error (in Ω).

RT is the maximum load resistance that the current transmitter can drive (in Ω).

For reliable operation over the long term, you should design for less initial cable resistance than this maximum value. This provides a safety factor to account for increase in resistance of terminations and wiring with age or weathering.

A sensible value to use for this safety factor would be 100 Ω (equal to 2 V at 20 mA).

For more information contact Ian Loudon, OmnIflex, +27 (0) 31 207 7466.



Credit(s)



Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

Power supply with scalability optimised
Schneider Electric South Africa Electrical Power & Protection
Schneider Electric has introduced the Easy UPS 3-Phase Modular to the South African marketplace. This robust uninterruptible power supply (UPS) is designed to protect critical loads while offering third-party verified Live Swap functionality.

Read more...
Prioritising arc flash safety
Comtest Electrical Power & Protection
Comtest has developed a range of thermal imaging and wireless testing tools from Fluke, designed to ensure safety is the top priority for engineers working in potentially dangerous arc flash zones.

Read more...
Hot Dip Galvanizers Association shines new light on renewable energy
Electrical Power & Protection
The Hot Dip Galvanizers Association of Southern Africa plays an important role in supporting the energy value chain – which spans clean, renewable and green energy – as it powers towards key sustainability targets.

Read more...
ACTOM supplies high-voltage equipment to wind farm project
ACTOM Electrical Machines Electrical Power & Protection
ACTOM High Voltage Equipment is currently in the process of manufacturing 400 kV and 132 kV high-voltage primary equipment for the Ummbila Emoyeni wind farm project in Mpumalanga.

Read more...
Energy measurement module for BL20 I/O System
Turck Banner Southern Africa Electrical Power & Protection
Turck’s BL20 energy measurement module enables precise monitoring of the energy consumption of single- or three-phase systems.

Read more...
Distributed energy resource management systems: a grid symphony
Schneider Electric South Africa Electrical Power & Protection
To listen to a symphony is one of the world’s great gifts. A conductor must ensure that instruments play beautifully as a whole and are kind to the ear and uplifting to the spirit yet shine in their individuality. The same can be said of a DERMS, which must effectively manage diverse energy sources to avoid compromising the grid’s integrity.

Read more...
Keeping mine outstations connected
Omniflex Remote Monitoring Specialists Industrial Wireless
Remote monitoring specialist, Omniflex has helped wireless data communications systems firm, Scan RF implement site-wide monitoring systems at the 17 000-hectare Kolomela iron ore mine in South Africa.

Read more...
Focus on energy sector infrastructure development can drive economic growth
Electrical Power & Protection
Post-election periods in South Africa often see a renewed focus on infrastructure development, with a specific emphasis on directing investments towards the energy sector. This strategic approach aims to accelerate economic growth, address energy challenges, and ultimately uplift the overall standard of living for the populace.

Read more...
Turning the continent into a global leader for green fuel
Electrical Power & Protection
Africa is at a turning point, with the potential to shift from being a supplier of raw materials to becoming a leader in advanced manufacturing, particularly in the growing green hydrogen market. For this transformation to happen, African countries must work together, combining their resources and talents to build a strong local economy.

Read more...
Epiroc showcases battery-electric drill rig at MINExpo 2024
Electrical Power & Protection
Epiroc recently showcased a demonstrator of the first ever Down-The-Hole SmartROC D65 battery-electric drill rig at the MINExpo exhibition in Las Vegas.

Read more...