With its equipment, the machine-building industry also exports safety standards to the global markets. In this way, the predominant type of protection in Germany and Europe, Intrinsic Safety (Ex i), is gaining increasing distribution. In the event of maintenance or replacement, measuring instruments in this category require no additional protective measures within the Ex area. This is convenient for the operator. However, there is one challenge that should not be underestimated: the proof of intrinsic safety.

Overview

For any explosion to occur, whether in a mine or in an industrial plant, three factors must come together: oxygen, flammable gas or dust, and also an ignition spark. As a result, the fundamental measures for explosion protection are derived from this. They are divided into three main types: The primary explosion protection is to prevent the formation of a hazardous explosive atmosphere, for example, by ventilation or extraction. The secondary explosion protection excludes the possibility that an ignition spark could let a potentially hazardous gas-air mixture explode. The tertiary explosion protection limits the effects that any explosion that occurs may have. For all electronic equipment, in general, there exists a risk of spark generation within the device. All measures which inhibit spark generation from the outset, prevent them from entering the explosive environment, or limit their energy, are counted as types of protection: Constructional design possibilities with a pressure transformer are, for example, the encapsulation of the electronic components with oil or sand (type of protection Ex m) or their flameproof enclosure (Ex d). Intrinsic Safety (Ex i), on the other hand, means an electronic solution. It relies on reducing the energy in a component – here in the transmitter – sufficiently so that it is always under the minimum ignition energy for an explosive atmosphere.

Ex i and the other types of protection are subject worldwide to various standards – in Europe this is the ATEX 94/9/EC product directive. The instrument marking compliant with the standards indicates for which Ex areas the specific product is approved. The WIKA pressure transmitter shown here is an intrinsically safe instrument which may be used in a permanently explosive atmosphere (protection type Ex ia). The instrument class 1/2G indicates that the sensor, for example, can be screwed into the side wall of a tank with explosive contents, with the electronics, however, installed outside and therefore in a less hazardous zone. (see Figure 1.)

Principles of operation

How does Ex i function in detail? Basically, the higher the electrical power, the higher is the chance of the (ignition) energy being released through the occurrence of a spark. With capacitances, sparks occur on the closing of an electrical circuit, with inductances, during the opening. Explosion protection through intrinsic safety thus means limiting the energy of the sparks. In an intrinsically safe pressure transmitter, such as the IS-3 from WIKA, it is ensured that, in normal operation as well as in the event of a fault, the minimum ignition energy of the hazardous area for which the instrument is approved is never exceeded. In addition, the surface temperature never exceeds the approved value, and thus, nor does it exceed the ignition temperature of the gas or dust mixture according to the temperature class defined in the standard.

This is mainly achieved through the limiting of voltage and current. Capacitance and inductance are also reduced in order to limit the energy of opening and closing sparks.

The design of the sensor has been matched to these low values for current and voltage.

In addition, for a safe power supply for the transmitter, an additional barrier is always required, for example a Zener barrier or an intrinsically safe isolated barrier. Effectively, a Zener barrier consists of a Zener diode and a fuse. When working on the circuit, such as during installation or maintenance, there is a risk that a short circuit could occur. In such an event, the fuse in the barrier could be destroyed and then, generally, the entire device must be replaced.

For this reason, the use of an intrinsically safe isolated barrier is recommended. By using an optocoupler (an integrated interconnection of an LED and a photo diode), this device galvanically isolates the intrinsically safe from the non-intrinsically safe circuit – in this way, the circuit is free from earth potential and thus enables a clean isolation of the earth potential in the safe and in the hazardous areas. In some cases, the barrier can already be integrated into the PLC. The PLC is located outside the Ex area, while the pressure transmitter (sticking with this example) is mounted in the hazardous area. The connection cables between both components must be correctly installed and specifically marked.

The proof

The ATEX standards do not only define the parameters for intrinsic safety. They also stipulate the proof, if an Ex i device and associated equipment are interconnected (in our example, pressure transmitter and isolated barrier). This subject confronts operators with a complex task, in which they are not safe from pitfalls and therefore must build in a considerable expense. First of all, they have to keep up to date on the current details of the standards. The procurement of individual components on an ATEX basis requires detailed checking: For which zones and explosion groups are the individual components approved? Is the barrier matched to the transmitter? Are the cables correctly dimensioned in order to ensure the required energy flow? Given the multitude of possible equipment variants, it can sometimes be difficult to make the right choice. For the proof of intrinsic safety, the individual approval and safety data of all components must subsequently be collated and recorded completely. Not every manufacturer makes, for example, the required ATEX approval certificate available for download. In this case, the document must be requested additionally.

With exception of petrochemical companies, Ex areas do not belong to the everyday routine of most plant designers and machine-building engineers. For this reason, experience shows us that for everyone with Ex i related tasks, two to three hours of engineering time should be estimated, per measuring point. Alternatively, the operator can turn to expert suppliers to the industry, in order to eliminate potential errors and, on top of that, save time. Against this background, WIKA has developed an ‘all-inclusive’ solution: The intrinsically safe pressure transmitter comes as part of a package with a matched barrier as well as all the data for the Ex i proof. This considerably simplifies the setting up of an ATEX-compliant measuring point and also the documentation connected with it.

For the proof of intrinsic safety, from a technical point of view, there needs to be a complete analysis of the circuit: The electrical parameters of the transmitter, isolated barrier and cable need to be matched and recorded. If the conditions specified in the standard are met, the interconnected measuring arrangement is considered to be intrinsically safe and can be installed.

In the documentation for intrinsic safety, the pin assignment of the entire system is also presented as a drawing.

The Ex i proof is part of the “explosion protection” chapter in the plant documentation. With this, operators ensure that their plant or machinery poses no risk to life or limb.



Credit(s)



Share this article:
Share via emailShare via LinkedInPrint this page

Further reading:

Field service regime key for effective PDS/CPS operation
IS & Ex
While their primary objective is to ensure the safety of people, proximity detection system and collision prevention system installations also have a direct bearing on other critical parameters such as equipment availability and productivity.

Read more...
World’s first 5G smartphone for ATEX and IECEx zone 1/21
Extech Safety Systems IS & Ex
i.safe MOBILE has launched the world’s first 5G smartphone for ATEX and IECEx zone 1/21. The intrinsically safe mobile device, which was also developed for use in 5G campus networks, offers companies great flexibility thanks to its wide range of possible applications, especially in the automation sector.

Read more...
Fully Ex-certified access point solutions for wireless communication
Pepperl+Fuchs IS & Ex
Pepperl+Fuchs now offers a wireless access point solution that is fully certified in accordance with ATEX/IECEx standards, and forms the basis for end-to-end Wi-Fi communication in hazardous areas.

Read more...
Secure, digital communication in potentially explosive atmospheres
Pepperl+Fuchs IS & Ex
Consistently digitalised processes in the smart factory are a matter of course today, but not in potentially explosive atmospheres. The systems and devices used in these areas must have optimal protection mechanisms to ensure maximum safety.

Read more...
Functional and compatible intrinsically safe loop approvals
Extech Safety Systems IS & Ex
With all the focus on IS loop approval, it is easy to forget to check that the loop will function correctly to see whether the field device has sufficient power (voltage & current) to operate over the full process range.

Read more...
OEM pressure sensor for mobile working machines
WIKA Instruments Sensors & Transducers
The MH-4-CAN, based on the MH-4, is a powerful, reliable and extremely resilient pressure sensor for mobile working machines.

Read more...
Upgrade your legacy alarm units
Omniflex Remote Monitoring Specialists IS & Ex
Darren Barratt, sales manager at alarm annunciator specialist Omniflex, explains the drawbacks of leaving outdated rack-based alarm annunciator systems in place, and why an upgrade might be simpler than you would expect.

Read more...
Magnetostrictive level transmitter
WIKA Instruments Level Measurement & Control
WIKA’s new model FLM-Tx-FLEX magnetostrictive level transmitter is used for high-accuracy, continuous level detection of liquids, including those with long insertion lengths.

Read more...
Chain hoist friction clutch tester
WIKA Instruments Motion Control & Drives
WIKA’s FRKPS chain hoist test set is a reliable and efficient way to test the friction clutch on your chain hoist.

Read more...
Cathodic protection system for hazardous environments
Omniflex Remote Monitoring Specialists IS & Ex
When NSW Ports in Australia embarked on a two-year programme to rehabilitate the structures and combat corrosion levels at its Bulk Liquid Berth 1, it commissioned Melbourne-based consultancy Infracorr to deliver a bespoke cathodic protection) system. To deliver the system safely, Infraccor engaged cathodic protection specialist Omniflex to support the hazardous area and remote monitoring aspects of the CP system design.

Read more...